Groth 1400 Bedienungsanleitung Seite 13

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 14
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 12
12
TABLE 6: LUBRICANTS – RECOMMENDATIONS
FASTENER LOCATION LUBRICANT – SEALANT MANUF. & PART NO.
Actuator Fastener Dry Moly Film Crown #6080 or equal
Stem Guide MS
2
Lubricant Fel-Pro [Loctite] #51048 or equal
Stem/Swivel Fitting Silicone Lubricant Dow Corning #33 or equal
Note: Lubricant selection must consider process environment.
TABLE 7: TROUBLESHOOTING GUIDE
PROBLEM INSPECTION SUGGESTED CORRECTIVE ACTION
Pilot Valve
Leak
Visual, audible or
vapor detector
Consult troubleshooting guide in specific pilot valve manual
Main Valve
Actuator Leak
Visual, audible or
vapor detector
Leakage at the actuator flange may be corrected by tightening
the fasteners adjacent to the leak path. If this is not successful,
it will be necessary to install a new gasket. Refer to
instructions on page 6.
Vapor leakage
from the valve
body outlet.
Visual, audible or
vapor detector
Leakage can occur at the valve body seat - FEP film interface;
other leak paths are the swivel seal or a torn actuator
diaphragm. After removing the upper actuator housing, lift the
pallet assembly off the seat and inspect for damage to the film
or foreign debris buildup on the seat or film. Clean or replace
the pallet diaphragm as required. Refer to page 6.
Vapor leakage
between the
valve body and
tank nozzle
Visual, audible or
vapor detector
Leakage between the flanges may be corrected by tightening
the fasteners. Follow mounting instructions listed on page 4.
The gasket may have deteriorated due to the chemical
environment; replace if required. The tank nozzle may be
warped, corroded or scratched. This will require resurfacing of
the flange face; note that a flat faced flange is recommended to
avoid potential damage to an aluminum valve body.
TABLE 8: ABBREVIATIONS
ANSI American National Standards Institute NPT National Pipe Thread
API American Petroleum Institute POV Pilot Operated Valve
BOM Bill of Materials PSIG Pounds/Sq. Inch – Gauge
DPHGM Diaphragm PTFE Fluoropolymer
FEP Fluorocarbon Film (Fluoropolymer) SS Stainless Steel
MAWP Maximum Allowable Working Pressure WC Water Column
MS
2
Moly – Disulfide
Seitenansicht 12
1 2 ... 8 9 10 11 12 13 14

Kommentare zu diesen Handbüchern

Keine Kommentare